Air curtains that keep the cold in while the door stays open.

Air curtains at store entrances, cool room doors, back of house and dock openings. Sized to the opening, commissioned with a meter in hand, then priced per store.

Air curtain mounted above a glazed cool room door in a bottle shop
An air curtain over the glazed cool room door in a bottle shop, between the cider cabinets. The head unit runs the full width of the door frame, which is the first thing to check on a unit that is already fitted.

An air curtain is a fan unit mounted at a doorway that blows a controlled sheet of air across the opening, so the warm air outside and the cold or conditioned air inside stay on their own sides while the door stands open. It works on momentum, which means it only works if the jet still has usable speed by the time it reaches the floor, and if that speed and the discharge angle are set for the opening it is on. Nextage sizes air curtains to the door, commissions them with a meter at the opening and reports the readings, across store entrances, cool room doors, back of house and dock openings nationally. Worked through the standard doorway method for the Melbourne cool room door we read, a curtain uses about 117 kWh a year in fan power and avoids roughly 1,270 to 3,160 kWh of refrigeration electricity, depending on how well it is set up. That is a calculation with its inputs shown, not a measurement.

0.31 to 0.77

Measured effectiveness of one air curtain on a cold store door: 0.31 as the installer left it, 0.77 once the jet speed and angle were set. Same unit, same door (Foster and others, International Journal of Refrigeration, 2006).

2.0 m/s at 150 mm

The jet speed near the floor that ASHRAE 90.1 requires before an air curtain may stand in for an entry vestibule, with the discharge angled at least 20 degrees towards the opening.

About 5 degrees

The rise we read at floor level inside a cool room when its door was opened with nothing protecting it: 4.8 degrees shut, 9.8 degrees open.

How it works

A jet with a job, not a fan over a door.

01

The jet has to reach the floor, across the whole width

An air curtain seals with momentum. Air leaves the unit fast, slows as it travels down, and whatever speed is left at ankle height is what actually holds the boundary. A unit rated to project three metres over a four metre opening is a fan and a draught. The same goes sideways: a 200 mm gap at one jamb is an open door as far as the air is concerned, and a short unit is the most common fault we find on curtains that were already there.

02

Temperature difference does the damage

At a cool room door, warm air rolls in across the top while cold air pours out across the bottom. That exchange is driven by the temperature difference across the opening far more than by any pressure difference, which is why the discharge is aimed slightly towards the warm side, and why the bottom of the door matters as much as the top.

03

Too much speed is a fault, not a margin

Run a curtain harder than the opening needs and the jet hits the floor and rebounds, dragging warm air back into the room it was meant to protect. Speed is trimmed on site, on stepless control where the unit has it, rather than left where it arrived.

04

Below zero is a different job

Above zero, moisture that condenses runs away. On a freezer opening it becomes frost and then ice: on the grille, on the floor and in the door track. Those openings need a family built for it, often two units with opposed jets, and where the moisture goes has to be part of the specification.

Illustration: an open cool room door with warm air flowing in across the top and cold air out across the bottom, beside the same door with an air curtain jet angled towards the warm side and reaching the floor
Illustration. Left, the exchange an open door runs on temperature difference alone. Right, where the jet has to still be moving for that to stop. The temperatures are our December 2024 readings.

The evidence

Where every figure on this page comes from

Four kinds of number get mixed up in air curtain sales copy. Each card says whose it is, and the full detail sits under it.

Our reading

4.8 to 9.8degrees, door shut then open

What an open door did to one cool room

Floor level, half a metre inside, door shut and then open with nothing running. With the curtain on and the door still open, the air 1.2 m up held 5.1 degrees.

Source: Site visit with the retailer's team, Melbourne, December 2024

The full detail

December 2024, a liquor store cool room in Melbourne, on a site visit run with the retailer's own team. The door is 920 by 1950 mm and the room holds 4 to 6 degrees. At floor level half a metre inside the door we read 4.8 degrees with the door shut and 9.8 degrees with it open and unprotected. With the curtain running and the door still open, the air 1.2 m up and a metre inside sat at 5.1 degrees, and at 1.8 m it sat at 4.1 to 4.3 degrees. Outside the door the jet was still moving at 2.09 m/s half a metre out, which is how we knew it was reaching the floor.

Our reading

10.8 to 12.0degrees at the slab, curtain on

The reading that went the wrong way

With the curtain running, the floor read warmer, not cooler. The probe was sitting in turbulence and rebound at the slab, so we now read half a metre up.

Source: Same visit, reviewed with the equipment maker's technical team

The full detail

At floor level, with the curtain running, the readings came back warmer rather than cooler. That looks like a failed install until you look at where the probe was: at the floor the jet is turbulent and part of it is rebounding off the slab. Reviewed with the equipment manufacturer's technical people, the guidance was to read half a metre above the floor rather than at it, aim the vanes straight or slightly out of the room, and trim the speed until the rebound stops. We publish this because it is the part of air curtain measurement that usually gets quietly dropped.

Peer reviewed

0.31 to 0.77effectiveness, before and after setup

Same unit, set up properly

Effectiveness of one curtain on a cold store door, as the installer left it and after the jet speed and angle were adjusted.

Source: Foster and others, International Journal of Refrigeration 29(5), 2006

The full detail

Foster, Swain, Barrett, D'Agaro and James measured a 1.0 m wide air curtain on a 1.36 m wide cold store entrance and reported an effectiveness of 0.31 as the installer had set it, rising to 0.77 once the jet velocity and angle were adjusted. Their model put the ceiling at 0.84. International Journal of Refrigeration, volume 29, 2006, pages 692 to 699. Same hardware, more than double the result, from the setup alone.

Test standard

2.0 m/sat 150 mm above the floor

What overseas codes count as a seal

ASHRAE 90.1 accepts a curtain in place of a vestibule only if it is tested to ANSI/AMCA 220 or ISO 27327-1 and still moves this fast near the floor.

Source: ASHRAE 90.1-2019, addendum ao

The full detail

Air curtain performance is tested under ANSI/AMCA 220 or ISO 27327-1:2009: airflow rate, how uniform the outlet velocity is, power draw, and how far the jet projects. An airflow figure with no test standard behind it is a marketing number, so it is worth asking which standard, and whether the rating was independently certified or self declared. Those two standards are also the gate in ASHRAE 90.1, which has allowed an air curtain in place of an entry vestibule since its 2019 edition, on conditions: tested to one of them, a jet of at least 2.0 m/s measured 150 mm above the floor across the whole opening, and the discharge angled at least 20 degrees towards the opening. The IECC and IgCC carry the same allowance. American codes, and the clearest published statement of what a curtain has to do before it counts as a seal.

Australian code

Not listedair curtains, in clause J5D5

NCC J5D5 does not name air curtains

An entrance to a conditioned space needs an airlock, a self closing, rapid roller or revolving door, or the like. A curtain alone is a comfort and running cost measure.

Source: NCC 2022 Volume One, clause J5D5

The full detail

NCC 2022 Volume One, clause J5D5, requires an entrance leading to a conditioned space to have an airlock, a self closing door, a rapid roller door, a revolving door or the like, with exceptions where the conditioned space is 50 square metres or less, and for a cafe, restaurant or open shop that keeps the first three metres inside its main entrance unconditioned. Air curtains are not named in that list. A curtain at a shop entrance is a comfort and running cost measure, or part of a performance solution that the certifier assesses. Anyone who tells you it satisfies J5D5 on its own should be asked to show you where.

Food rules

8.13 m/sat a food premises service door

Keeping insects out takes far more air

The jet speed NSF/ANSI 37 sets at a service door, against 3.05 m/s at a customer entrance. A comfort unit reaches neither.

Source: NSF/ANSI 37; FSANZ Safe Food Australia; AS 4674

The full detail

Standard 3.2.3 of the Food Standards Code requires food premises to exclude dirt, dust, fumes, smoke and other contaminants as far as is practicable, and the FSANZ guide Safe Food Australia lists positive air curtains at entrances among the ways to do it. AS 4674, withdrawn by Standards Australia but still handed out by councils, names air curtains alongside self closing doors, mesh screen doors and plastic strips. Where the brief is flying insects rather than energy, NSF/ANSI 37 sets a far higher bar: about 8.13 m/s at a service door and 3.05 m/s at a customer entrance, which a comfort unit will not produce.

Comparison

Air curtain, strip curtain, or a door?

All three close the same gap. They fail in different ways, and how they fail is usually what decides the doorway.

ConsiderationAir curtainPlastic strip curtainDoor
Sight line through the openingClear. Nothing hangs in the openingClouds, scratches and yellows in service, so staff stop trusting what is behind itShut, unless it is glazed
Trolleys, pallets and staffNothing to push through, which is why it suits picking trafficStrips catch on stock and trolley corners, and torn strips stay tornHas to be opened, or gets chocked open, which is how the seal is lost
Food areas and cleaningCasing and grille wipe down, and nothing touches stock on the way pastNeeds scheduled cleaning and replacement, and it does touch stockSeals and gaskets to clean and check
With the power offNothing. It is an active device and it needs supplyStill hanging thereStill shuts
MaintenanceGrille and filter cleaning, fan bearings, and a speed check after anything changes at the doorStrip and rail replacement, on a cycleHinges, closers, gaskets and tracks
What the rules nameNamed in the FSANZ guidance and in AS 4674 for contaminants and pests. Not named in NCC J5D5Named in AS 4674 as plastic stripsSelf closing, rapid roller and revolving doors are what NCC J5D5 names
Where it usually winsOpenings that must stay clear and in near constant use: entrances, cool room doors on picking runs, docksLow traffic cool room doors where appearance does not matterAnywhere the opening can actually be shut between uses

At a lot of cool room doors the honest answer is both: keep the door for the hours nothing is moving, and put a curtain on it for the hours it stands open. What does not work is leaving strips hanging in front of a new air curtain, which breaks the jet up before it gets anywhere. One or the other in the traffic path.

Cost and carbon

What a curtain is worth at one cool room door

A calculation, not a measurement. It takes the Melbourne door we read, puts it through the standard engineering method for air flowing through a cold room doorway, and sets what the curtain saves against what its own fans use. Every input is in the next table, so you can change the ones that do not match your door.

Per year, door open 4 hours a dayAs installed, 0.31Modelling default, 0.5Set up properly, 0.77
Refrigeration electricity avoided1,274 kWh2,055 kWh3,164 kWh
Curtain fans, running only while the door is open117 kWh117 kWh117 kWh
Net electricity avoided1,157 kWh1,938 kWh3,047 kWh
Carbon avoided in Victoria, at 0.78 kg per kWh0.90 tonnes1.51 tonnes2.38 tonnes
Power cost avoided, at an assumed 25c per kWh$289$484$762

Two things decide the answer more than the unit does. Setup is one: the same curtain is worth more than two and a half times as much set up properly as it is as installed. Control is the other: run the fans around the clock instead of on a door switch and they use 701 kWh a year, which cuts the badly set curtain's net saving to 573 kWh and leaves the well set one near 2,460. Victoria is used because the door is in Melbourne; in NSW the net carbon would be 0.74 to 1.95 tonnes. None of this is a forecast for your door.

The inputs

Every number the calculation uses

InputValueWhere it comes from
Door920 by 1950 mmMeasured, the Melbourne cool room door, December 2024
Inside the room5 degreesMeasured, the middle of the 4 to 6 degrees the room held
Outside the door18.5 degreesMeasured just outside the door at 18.6 to 18.8 degrees, rounded down
Humidity60 per cent outside, 85 per cent insideAssumed. Wetter store air makes the saving larger
Heat through the open door8.4 kWGosney and Olama, Proceedings of the Institute of Refrigeration, 1975: the doorway method ASHRAE uses, with its 0.8 flow factor for a temperature difference over 11 degrees
Curtain effectiveness0.31, 0.5 and 0.770.31 and 0.77 measured by Foster and others, International Journal of Refrigeration, 2006. 0.5 is the air curtain default in the US Department of Energy's EnergyPlus building model
Refrigeration efficiency3 units of heat moved per unit of electricityAssumed. A less efficient plant makes the saving larger
Curtain fans80 WRated fan power of the 1 m unit quoted for this door, from its spec sheet
Door open4 hours a day, every dayAssumed. Double it and the saving doubles
Power price25c per kWhAssumed. A round number, not a tariff
Carbon0.78 kg per kWhNational Greenhouse Accounts Factors 2025, Victoria

Specification

What gets measured before a unit is chosen

Nine things decide which unit goes over a door. A quote produced without them is a price on a guess, and the guess usually turns up later as a curtain running flat out against a door that opens twice an hour.

What we measureWhat it decidesWhat goes wrong when it is guessed
Clear opening widthUnit length, or how many units sit in lineA unit shorter than the opening leaves an unsealed strip at one jamb, and the air takes it
Mounting height above the floorWhich family, because the rated projection has to exceed that heightA unit rated to three metres over a four metre door has no speed left at the floor
Room or chamber temperatureAbove zero, or a freezer family with the moisture designed forFrost and then ice on the grille, the floor and the door track: a defect call, not a saving
Openings per hour, and what moves throughSpeed setting, and whether the unit runs on a door contact or continuouslyA unit wired to run 24 hours to protect a door that opens 30 times a day
What else moves air nearbyExhaust fans, kitchen hoods and the store air conditioning all pull against the jetThe curtain gets blamed for a pressure problem that somebody else's fan is causing
Noise limit at that positionThe unit's rating in dB(A) at five metres, against how close staff and customers standA unit over a service counter that staff quietly switch off, which is how most curtains stop working
Power available at the head of the doorSingle or three phase, breaker size, cable section, and whether heating is electricA heated unit specified where the board has no spare capacity, so the job stops at the switchboard
Fixing and access above the openingBrackets, rail supports, suspension cables, vibration mounts, and how the grille gets cleanedA surface unit specified where the shopfit bulkhead will not carry it or will block the discharge
What the door is actually forEntrance, cool room, back of house, dock, or a food area with an insect problemA comfort unit sold against an insect brief at a third of the jet speed NSF/ANSI 37 asks for

All nine come off one site visit, and they are the same nine at every store. That is what turns a doorway by doorway argument into one specification per door type across the fleet.

Photos

What the measurement looked like

Phone photos from the December 2024 visit to one Melbourne cool room door, taken with the retailer's team. A handheld anemometer reads air speed and temperature together, and a tape laid out from the door fixes where each reading was taken.

An air curtain mounted over a cool room door in a bottle shop, the door standing open onto shelving inside the cool room
The door, open, with the curtain over the head. The opening is 920 by 1950 mm.
An anemometer on a speckled floor reading 2.09 metres a second and 18.6 degrees
Outside the opening, half a metre out, curtain running: 2.09 m/s at 18.6 degrees. The jet is still moving when it reaches the floor.
An anemometer display reading 0.73 metres a second and 9.8 degrees, beside a measuring tape
Door open, nothing running, at floor level half a metre in: 0.73 m/s and 9.8 degrees, against 4.8 with the door shut.
An anemometer held up at shelf height reading 0.04 metres a second and 5.1 degrees
Curtain running, door still open, 1.2 m up and a metre inside: 0.04 m/s and 5.1 degrees. Still air, and the room holding.

The range

Twelve families, because a dock door and a service window are different problems.

01

Unheated entrance curtains

Air only, for an air conditioned shopfront where the job is holding the boundary rather than adding heat. Usually single phase, mounted in or on the bulkhead over the door, in families rated to project about three metres.

02

Electrically heated curtains

Where a cold climate entrance draught is a real comfort complaint, heating stages go into the same air path. The heat is the load: it moves the problem onto the switchboard, so the available supply is checked before the unit is chosen rather than after.

03

Hot water heated curtains

Where the building already has a heating water circuit, the coil runs off that instead of adding electrical load. It needs pipework and a valve at the door, so it belongs in a fitout or a refurbishment rather than a retrofit at a trading store.

04

Cool room door curtains, above zero

The workhorse in retail back of house: higher jet speed for the height, stepless speed control so it can be trimmed on site, adjustable outlet vanes so the jet can be aimed, and a casing that cleans. Rated for chambers above zero, and the door contact is an accessory worth having rather than an upsell.

05

Freezer and sub zero openings

Below zero the humidity becomes frost and then ice. These openings take a higher pressure family, sometimes two units with opposed jets, and the specification has to answer where the moisture goes as well as what the jet speed is. It is the application most often sold the wrong unit.

06

Industrial and high openings

Roller shutters, dock doors and warehouse openings, in families rated to about seven metres high. Bigger motors, three phase supply, and fixing that has to be engineered rather than screwed to a bulkhead.

07

Insect control curtains

Built for the jet speeds NSF/ANSI 37 asks for at food premises openings, which are several times what a comfort unit produces. This is the family to quote when the brief came out of a food safety audit or a pest report, not the cheapest unit that fits the width.

08

Compact units for small openings

Service windows, pass throughs and small back doors, where a full size unit will not fit and the jet has a short drop to cover. NSF/ANSI 37 treats a service window as its own case, with the jet checked a third of the way down from the sill rather than near the floor.

09

Recessed and cassette units

For shopfits that will not carry a surface box: the unit sits in the ceiling void and only the grille shows. It has to be planned with the ceiling, and access for cleaning has to be planned with it.

10

Stainless steel and washdown units

Wet, salty or corrosive areas: wash bays, food processing, coastal loading areas. Higher ingress protection and a casing that can take a hose, which a standard painted steel unit cannot.

11

Vertical and side mounted units

Where there is no head height above the opening, the unit mounts at the jamb and blows across instead of down. It suits glazed shopfronts with no bulkhead, and some drive through openings.

12

Trailer and dock curtains

For refrigerated trailers and dock levellers, where the opening is not part of the building at all and the unit travels with the vehicle or sits in the dock seal.

Delivery

Measure, specify, install, commission.

Same order every store. The order is what makes store 40 match store 1.

  1. Measure

    Attend the door and read air velocity and temperature at set distances and heights, in each state: door shut, door open, and with anything already fitted running. Written up with the conditions on the day, because a 35 degree afternoon and a mild morning are not the same test.

  2. Specify

    Unit length to the clear opening, family to the temperature and the mounting height, control to how the door is actually used, and the power supply and the fixing confirmed before anything is ordered.

  3. Install

    Fitted out of trade hours where the door is in a customer area, with the electrical connection done by a licensed electrician on the same visit rather than left as somebody else's problem.

  4. Commission

    Speed and vane angle set with a meter at the opening, not by ear, then remeasured. The readings and the final settings go in the completion pack with the photos, so the next store starts from a known number.

Supply and install

Supplied, ordered and fitted for you.

No products to order, fixings to buy or trades to chase. One call, and it arrives fitted.

Tell us the site and roughly how many. We walk it and come back with a measured quote.

  1. We measure

    A site walk sets what goes where, and how many.

  2. We order

    The right product, size and quantity, delivered to site.

  3. We organise

    Access, inductions and timing around your trading hours.

  4. We install and photograph

    Fitted by our crews, with before and after photos when it is done.

What Nextage does

  • Instrumented measurement at the opening first: air velocity and temperature, before anything is ordered
  • Unit sized to the clear opening and the mounting height, not to a catalogue page
  • One specification per door type across the fleet, so store 40 gets what store 1 got
  • Supply, installation and the licensed electrical connection on the same visit
  • Commissioning with a meter: speed and vane angle set at the opening, then remeasured
  • A price per site, so a rollout stages against the capital cycle
  • Readings, final settings and photos per store in one completion pack

What this is not

  • A guaranteed saving percentage before we have measured your door. We measure, we do not promise a number in advance
  • Refrigeration plant design, replacement or servicing, which is a licensed refrigeration trade
  • A sealed cool room that has to hold temperature while nobody is using the door. A curtain is not a door
  • A doorway that could simply be kept shut. If that is the answer we will say so, and it costs nothing
  • Sign off that a curtain satisfies NCC J5D5 at an entrance. That is the certifier's call on a performance solution, not a supplier's

About the published figures

Four kinds of figure appear above, and they are labelled on purpose. The research result is somebody else's cold store. The code thresholds are test conditions, and two of the three codes quoted are not Australian. The insect control velocities belong to NSF/ANSI 37. The only readings here that are ours came off one Melbourne cool room door in December 2024, a 920 by 1950 mm opening on a room holding 4 to 6 degrees, and they are published with the reading that went the wrong way left in. The cost and carbon table is a calculation built on that door, a published method and inputs that are labelled where they are assumed. None of it is a forecast for your doors. What we will tell you about your stores is what the meter says at your openings, before and after. If that does not support the spend, you will get that answer too.

FAQ

About Air curtains

What does an air curtain actually do?

It blows a controlled sheet of air across a doorway so the air on each side stays where it is. At a cool room door that means less cold air pouring out at the bottom and less warm air rolling in at the top while the door is open. At a store entrance it holds the conditioned air in, and in a food area a unit built for it also makes the opening harder for flying insects and airborne dirt to cross.

Do air curtains save energy?

A correctly sized and correctly set up curtain cuts the air exchange through an open door, and less exchange is less load on the refrigeration or the air conditioning. How much depends on the opening, how often it is open and how the unit is set, which is why the saving has to be measured at your door rather than taken off a brochure. Published research on a cold store door found the same unit going from 0.31 to 0.77 effectiveness on setup alone. Worked through for one Melbourne cool room door standing open four hours a day, the calculation on this page puts the net saving at about 1,160 kWh a year as typically installed and about 3,050 kWh set up properly, against 117 kWh for the curtain's own fans.

How much carbon does an air curtain save?

On the worked example on this page, one Melbourne cool room door open four hours a day, about 0.9 tonnes a year as typically installed and 2.4 tonnes set up properly, at the Australian Government's 2025 factor for Victoria. It is a calculation from a published doorway method with every input shown, not a measurement, and the biggest lever in it is the setup, not the unit.

Does an air curtain meet NCC Section J at a shop entrance?

Not on its own. NCC 2022 clause J5D5 names an airlock, a self closing door, a rapid roller door, a revolving door or the like for an entrance leading to a conditioned space, and an air curtain is not in that list. It can form part of a performance solution, which the building certifier assesses, and it is often worth fitting purely for comfort and running cost. Anyone who tells you it ticks J5D5 by itself should be asked to point at the clause.

Do air curtains keep flies out?

Only if the unit was built for it. NSF/ANSI 37, the standard written for air curtains at food premises openings, sets a jet speed of about 8.13 m/s at a service door and 3.05 m/s at a customer entrance. A comfort unit chosen for an entrance draught runs well under that, so it will not do the insect job. If the brief came out of a food safety audit or a pest report, say so, because it changes the family of unit.

Can an air curtain replace a cool room door?

No. A curtain reduces the exchange while the door is open. It cannot hold a room at temperature when nobody is using the door, and it does nothing at all with the power off. The usual answer at a busy cool room is both: the door for the quiet hours, the curtain for the hours it stands open.

Will an air curtain work on a freezer door?

There are families built for sub zero openings, often two units with opposed jets, but it is a different specification and a harder one. Below zero the moisture in the incoming air turns to frost and then ice, on the grille, on the floor and in the door track, so where that moisture goes has to be designed rather than discovered. A unit rated for chambers above zero fitted to a freezer opening is the most common wrong purchase in this category.

How high can an air curtain be mounted?

It depends on the family. Commercial entrance and cool room units are commonly rated to project about three metres, and industrial families go to about seven metres. The rating matters more than the look of the unit: mounted above its rated projection, the jet arrives at the floor too slow to hold anything, and the curtain becomes an expensive draught.

How do you size an air curtain for a doorway?

Length to the clear opening width first, so the jet covers the whole gap, using units in line where one will not reach. Then the family and the speed to the mounting height and the temperature difference, then the control to how the door is actually used. We take air velocity and temperature readings at the opening before specifying, because door traffic, exhaust fans and the store air conditioning all change the answer.

Heated or unheated?

Unheated is right for most Australian retail entrances, where the store is air conditioned and the job is holding the boundary. Heating earns its place where a cold climate entrance draught is a genuine comfort complaint, and it can be electric or run off an existing heating water circuit. Electric heating is the load to watch: it often needs three phase and spare capacity at the board, which makes it a switchboard question before it is an air curtain question.

How loud is an air curtain?

Manufacturers publish a noise rating, commonly in dB(A) at five metres, and a unit usually has a quiet setting and a high one. It matters most over a service counter or near a checkout, because a unit that is too loud for the people standing under it gets switched off, and a switched off curtain saves nothing. The rating and the listening distance both belong in the specification.

What power supply does an air curtain need?

An unheated commercial unit is typically single phase with a modest fan load, often well under a kilowatt for a domestic sized opening. Electrically heated and industrial units are a different matter and commonly need three phase and their own circuit. Breaker size and cable run are checked at the survey, so the electrical work is quoted with the unit instead of stopping the install.

Should it run all the time, or on a door switch?

On a door contact wherever the door is genuinely closed between uses, which is most cool room doors. Continuous running suits an opening that stands open all trading day. Wiring a continuous run to a door that opens thirty times a day is a running cost with no benefit, and it is one of the first things we change on curtains that were already there. In the worked example on this page, running the fans around the clock instead of on the door costs 584 kWh a year more, which is half the net saving of a curtain left at its installed settings.

What maintenance does an air curtain need?

Keep the inlet grille and any filter clean, because a blocked inlet costs jet speed straight away and cool room installs in humid areas clog faster. Beyond that it is fan bearings, and a speed check any time something changes at the door: a new door leaf, a new exhaust fan, a shopfit that moves the bulkhead. Ours get remeasured rather than assumed.

Why do you measure before quoting?

Because the number that matters is the one at your door. A data sheet describes a test opening in a laboratory, not a store entrance with a kitchen exhaust forty metres away and a cool room door that stands open through the morning pick. We read air velocity and temperature at the opening in each state before anything is ordered, and again after commissioning, so the business case is built on your readings.

Our shopfront has no bulkhead above the door. What then?

Vertical units mounted at the jamb blow across the opening instead of down, and recessed units sit in the ceiling void with only the grille showing. Both are normal answers to a glazed shopfront with nowhere to hang a surface box. The trade off is planning: a recessed unit has to be coordinated with the ceiling, and with how the grille will be cleaned.

What is the difference between an air curtain and a strip curtain?

A strip curtain is plastic hanging in the opening: cheap, passive, and still working with the power off, but it clouds and tears, catches trolleys and stock, and staff stop trusting what is behind it. An air curtain leaves the opening clear, and needs power and setup to do anything at all. Do not fit both in the same traffic path, because strips hanging in front of a curtain break the jet up before it gets going.

Can you roll this out across stores in several states?

Yes, and that is the normal shape of this work. A sample of stores is measured, one specification is set per door type, each store is priced, and the rollout stages against the capital cycle under one accountable team, with readings and photos filed per store.

Start with one door.

We measure the opening before anyone orders a unit.